1、The unit uses waste heat and waste heat for refrigeration,almost no energy is needed.Operation cost is very low;
2、Each chamber inside the unit is designed with vacuum insulation layer to reduce internal heat loss and improve unit efficiency;
3、The COP of low temperature hot water absorption lithium bromide refrigeration unit and 0.1MPa steam type absorption lithium bromide refrigeration unit is above 0.72;
4、The COP of vapor type (0.6 MPa, 0.8 MPa) absorption lithium bromide chiller is above 1.35;
Shandong Lucy New Energy Technology Co., Ltd. has been focusing on product innovation and performance improvement, constantly optimizing the structure and performance of absorption refrigeration units, and has made great progress in waste heat recovery and solar air conditioning. The company now has absorption air-conditioning units (5kW cooling capacity), and solar air-conditioning systems (11 years) with longest operation time in China, It is exported to Europe, Southeast Asia, America, Australia, West Asia and other regions and countries.
type |
energy |
application |
|
standard product |
hot water absorption chiller |
hot water ,conduct oil(72-90 ºC) |
solar energy generator industry waste heat. |
assemble solar hot water absorption chiller |
solar hot water (72-90 ºC)(72-90 ºC) | school ,hall ,office, villa . | |
steam operate double effect absorption chiller | steam (6bar ,8bar) | plant station, industry waste steam | |
exhaust gas fired absorption chiller | high temperature exhaust gas (≥175 ºC) | generator , boiler exhaust gas | |
natural gas fired absorption chiller | natural gas, gas ,biogas, diesel | hospital, hall, hotel, office. | |
Non-standard models | two stage absorption chiller | low temperature hot water(≥65ºC) | industry hot water or solar hot water |
twin times absorption chiller | big temperature in/out waste heat (90-70 ºC) | waste industry heat | |
automatically change single /double effect absorption chiller | automatically change single /double effect absorption chiller | industry waste heat | |
steam operate single effect absorption chiller | steam (1bar, 4bar) | plant, paper mill, industry steam | |
exhaust &hot water absorption chiller | generator jacket water and exhaust gas | CCHP system | |
small type absorption air cooling and air cold chiller | hot water (72-90 ºC) | villa family |
Integrated solar energy small absorption refrigeration unit
Solar air conditioning is driven by clean solar energy. the system meet the requirements of environmental protection. It not only saves power and fuel, energy conservation and environmental protection, but also almost zero emission. It is fully meet the requirements of sustainable development strategy.
Another advantage of solar air conditioning is: the application of solar air conditioning coincides with the season. The higher the temperature in summer, the more cooling capacity people need. At this time, the stronger the sunlight radiation, the greater the output energy of solar energy and the cooling capacity provided by solar air conditioning also reaches a large value. Solar energy is inexhaustible. Solar air conditioning can save more than 90% electricity
The unit integrates absorption chiller, cold water pump, cooling water pump, hot water pump, valve and filter, which is convenient for users to install.
Integrated solar energy small absorption refrigeration unit
Model number |
TX-11 | TX-23 | TX-35 | TX-58 | TX-115 | TX-175 | TXZ-230 | TX-290 | TX-350 | ||
Rated cooling capacity kW |
11.5 | 23 | 35 | 58 | 115 | 175 | 230 | 290 | 350 | ||
Hot water |
Hot water flow m³/h |
2.9 | 5.8 | 8.6 | 14.3 | 28.5 | 42.8 | 57.0 | 70.0 | 85.3 | |
Inlet and outlet temperature |
90 / 85℃ | ||||||||||
Import and export pipe diameter |
DN25 | DN40 | DN40 | DN50 | DN65 | DN80 | DN100 | DN100 | DN125 | ||
Pressure drop MPa |
0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | ||
cold water |
Cold water flow m³/h |
2.0 | 4.0 | 6.0 | 10.0 | 20.0 | 30.0 | 40.0 | 50.0 | 60 | |
Inlet and outlet temperature |
15 / 10℃(12 / 7℃) | ||||||||||
Import and export pipe diameter |
DN25 | DN25 | DN32 | DN50 | DN65 | DN65 | DN80 | DN80 | DN100 | ||
Pressure drop MPa |
0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | ||
Cooling water |
Cooling water flow m³/h |
5.0 | 10.0 | 15.0 | 25.0 | 50.0 | 75.0 | 100 .0 | 120.0 | 150.0 | |
Inlet and outlet temperature |
30/35℃(29 / 34℃) | ||||||||||
Import and export pipe diameter |
DN32 | DN40 | DN50 | DN65 | DN80 | DN100 | DN125 | DN150 | DN150 | ||
Pressure drop MPa |
0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | 0.08 | ||
power consumption kW |
1.0 | 1.7 | 2.3 | 2.8 | 5.3 | 10.0 | 13.8 | 17.5 | 21.2 | ||
Dimensions |
length mm |
1500 | 1500 | 1900 | 2250 | 3500 | * | * | * | * | |
width mm |
1320 | 1320 | 1320 | 1320 | 1700 | * | * | * | * | ||
height mm |
1810 | 1810 | 1810 | 2100 | 2400 | * | * | * | * | ||
Shipping weight kg |
1150 | 1150 | 1300 | 2050 | 3300 | * | * | * | * |
Note:
1. The above main machines include lithium bromide unit, computer control box and cooling unit. Cooling tower, cold water pump, cooling water pump, hot water electric control valve, cold water and cooling water filter, vacuum pump, etc.
2. The fouling of chilled water is 0.086m2 ℃ / kW.
3. Wet bulb temperature: 27 ℃.
Lithium bromide-water absorption refrigeration device is mainly composed of four parts: generator, condenser, evaporator and absorber. Its basic working principle is as follows:
(1) Use the working heat source (such as water vapor, hot water and gas, etc.) to heat the dilute solution delivered from the absorber by the solution pump in the generator, and evaporate the water in the solution.
(2) Water vapor enters the condenser, and is condensed into refrigerant water by the cooling medium.
(3) The refrigerant water enters the evaporator through throttling, absorbs the heat in the refrigerant water and is excited into water vapor.
(4) The concentrated solution remaining after the occurrence process in the generator enters the absorber, mixes with the water vapor from the evaporator, absorbs the water vapor and returns to its original concentration, becoming a dilute solution. The dilute solution enters the generator through the solution pump and continues to circulate.
1、The unit uses waste heat and waste heat for refrigeration,almost no energy is needed.Operation cost is very low;
2、Each chamber inside the unit is designed with vacuum insulation layer to reduce internal heat loss and improve unit efficiency;
3、The COP of low temperature hot water absorption lithium bromide refrigeration unit and 0.1MPa steam type absorption lithium bromide refrigeration unit is above 0.72;
4、The COP of vapor type (0.6 MPa, 0.8 MPa) absorption lithium bromide chiller is above 1.35;
5、The COP of direct fired absorption lithium bromide chiller is above 1.35;
6、Leak detection for five consecutive processes to ensure that the unit has no fault due to leakage;
7、High intelligent automatic control. The unit can be started up and shut down by "one key", with the function of fault alarm dilution and shutdown.
8、The control system directly or indirectly controls the cooling water pump, cooling water pump and cooling tower fan, which improves the overall efficiency of solar air conditioning system by 25%;
9、The color LCD touch screen is used in the computer automatic control, which can dynamically display the operating conditions of the unit. The screen has the function of fault recording and real-time recording of parameter operation curve.
10、The first-line brand control components are adopted: Omron CP1 series PLC, OmronLY2N-Jseries relay, Schneider IC65series circuit breaker, Schneider LC1-Dseries contactor, WEINVIEWtouch screen, WILO water pump of Germany. These components ensure the reliability of the control system hardware.
11、Fine workmanship ensures the service life of the unit is 23 years and 30 years.