When the unit is working, the light solution in the absorber is transported to the heat exchanger a by the generating pump in two ways, and then enters the generator after heat exchange and temperature rise.When the dilute solution entering the generator was heated to the evaporate point by the working steam, the refrigerant steam is generated, which is go into the condenser through throttling, finally cooled into refrigerant water. The refrigerant water produced by the generators is combined by the condenser water collector and then led into the evaporator.
When the unit is working, the light solution in the absorber is transported to the heat exchanger a by the generating pump in two ways, and then enters the generator after heat exchange and temperature rise.When the dilute solution entering the generator was heated to the evaporate point by the working steam, the refrigerant steam is generated, which is go into the condenser through throttling, finally cooled into refrigerant water. The refrigerant water produced by the generators is combined by the condenser water collector and then led into the evaporator.
The refrigerant water absorbs the heat of the refrigerant water in the evaporator and intensifies into water vapor. In the generators, the heavy solution enters the absorber and mixes with the water vapor from the evaporator. The water vapor is absorbed and recovered to the original concentration and becomes dilute solution. The dilute solution enters into the generator through the generator pump and continues to circulate.
Technical Parameters of 0.1MPa Steam-operated Single Effect Absorption chiller
Model |
XZ- 23 |
XZ- 35 |
XZ- 58 |
XZ- 115 |
XZ- 175 |
XZ- 230 |
XZ- 290 |
XZ- 350 |
XZ-465 |
|
Cooling Capacity kW |
23 |
35 |
58 |
115 |
175 |
230 |
290 |
350 |
465 |
|
Working Steam
|
Steam Consumption |
47.6 |
72.5 |
120.1 |
238.1 |
362.3 |
476.2 |
600.4 |
724.6 |
962.7 |
Steam Pressure |
0.1MPa |
|||||||||
Inlet Dia. |
DN32 |
DN32 |
DN32 |
DN32 |
DN50 |
DN50 |
DN50 |
DN50 |
DN50 |
|
Outlet Dia. |
DN25 |
DN25 |
DN25 |
DN25 |
DN25 |
DN25 |
DN25 |
DN25 |
DN25 |
|
Chilled Water
|
Flow rate m³/h |
4 |
6 |
10 |
20 |
30 |
40 |
50 |
60 |
80 |
Inlet/Outlet Temp. |
12 / 7℃ |
|||||||||
Inlet / Outlet Dia. |
DN32 |
DN40 |
DN40 |
DN50 |
DN50 |
DN65 |
DN65 |
DN80 |
DN100 |
|
Pressure Loss MPa |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
|
Cooling water
|
Flow rate m³/h |
10 |
15 |
24 |
48 |
74 |
97 |
122 |
147 |
196 |
Inlet Temp. |
32/37℃ |
|||||||||
Inlet / Outlet Dia. |
DN40 |
DN50 |
DN65 |
DN80 |
DN80 |
DN100 |
DN150 |
DN150 |
DN175 |
|
Pressure Loss MPa |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
|
Dimen sion |
Length mm |
1010 |
1010 |
1430 |
1800 |
2550 |
2755 |
3250 |
3250 |
3250 |
Width mm |
785 |
785 |
785 |
920 |
920 |
920 |
970 |
1110 |
1350 |
|
Height mm |
1622 |
1622 |
1622 |
1820 |
1820 |
1820 |
1990 |
2150 |
2150 |
|
Power Consumption kW |
0.3 |
0.3 |
0.4 |
0.5 |
0.6 |
0.6 |
0.9 |
0.9 |
1.1 |
|
Shipping Weight kg |
720 |
820 |
860 |
1000 |
1500 |
1700 |
1800 |
1900 |
2000 |
Note:
1. Fouling factor for chiller water is 0.086m2℃/kW.
2.Condensation temperature: ≤85℃
Model |
XZ- 580 |
XZ- 700 |
XZ- 930 |
XZ- 1150 |
XZ- 1450 |
XZ- 1750 |
XZ- 2300 |
XZ- 2900 |
XZ-3500 |
|
Cooling Capacity kW |
580 |
700 |
930 |
1150 |
1450 |
1750 |
2300 |
2900 |
3500 |
|
Working Steam |
Steam Consumption kg/h |
1200.8 |
1449.3 |
1925.5 |
2381.0 |
3002.1 |
3623.2 |
4761.9 |
6004.1 |
7246.4 |
Steam Pressure |
0.1MPa |
|||||||||
Chilled Water |
Inlet Dia. |
DN65 |
DN65 |
DN80 |
DN80 |
DN100 |
DN100 |
DN100 |
DN150 |
DN150 |
Outlet Dia. |
DN40 |
DN40 |
DN65 |
DN65 |
DN80 |
DN80 |
DN80 |
DN100 |
DN100 |
|
Flow rate m3/h |
100 |
120 |
160 |
198 |
249 |
301 |
396 |
499 |
602 |
|
Inlet/Outlet Temp. |
12 / 7℃ |
|||||||||
Inlet / Outlet Dia. |
DN100 |
DN125 |
DN125 |
DN150 |
DN150 |
DN175 |
DN200 |
DN250 |
DN300 |
|
|
Pressure Loss MPa |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
Cooling water
|
Flow rate m3/h |
244 |
295 |
392 |
484 |
611 |
737 |
969 |
1222 |
1474 |
Inlet Temp. |
32/37℃ |
|||||||||
Inlet / Outlet Dia. |
DN200 |
DN175 |
DN175 |
DN300 |
DN350 |
DN350 |
DN400 |
DN400 |
DN450 |
|
Pressure Loss MPa |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
|
Dimen sion |
Length mm |
3105 |
3470 |
4100 |
5300 |
5400 |
5400 |
6000 |
6450 |
7100 |
Width mm |
1160 |
1300 |
1300 |
1300 |
1600 |
2000 |
2000 |
2300 |
2300 |
|
Height mm |
2100 |
2200 |
2300 |
2400 |
2400 |
2753 |
2753 |
2800 |
3200 |
|
Power Consumption kW |
1.1 |
1.5 |
1.7 |
2.5 |
4.3 |
5.6 |
6.5 |
6.5 |
7 |
|
Shipping Weight kg |
5300 |
6700 |
8000 |
9300 |
12800 |
16000 |
20500 |
27000 |
32000 |
|
|
|
|
|
|
|
|
|
|
|
|
Note:
1. Fouling factor for chiller water is 0.086m2℃/kW.
2.Condensation temperature: ≤85℃
The refrigerant water absorbs the heat of the refrigerant water in the evaporator and intensifies into water vapor. In the generators, the heavy solution enters the absorber and mixes with the water vapor from the evaporator. The water vapor is absorbed and recovered to the original concentration and becomes dilute solution. The dilute solution enters into the generator through the generator pump and continues to circulate